- 3992796
Features:
- Model Number: PAD300-DUCTR
- Item Number: 3992796
- Detects Smoke in Building HVAC Ducts
- Ships Complete with Housing and Head
- Compatible with Addressable IPA and AFC/ARC Series Panels
- SLC Class A, Class X & Class B
- Installation Without Removing the Head
- Listed Air Velocity of 100 to 4,000 ft/minute
- No Screens or Filters in Housing
The PAD300-DUCTR is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors. Air sampling is accomplished by two (2) tubes which protrude into the duct. An exhaust tube of one (1) standard length (7”) is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined, the air intake sampling tubes must be ordered.
Specifications
- Duct Detector Model Number - PAD300-DUCTR
- Operating Voltage - 24 VDC
- Current Draw - 500 μA
- Detector Head Model - PAD300-DD
- Detector Head Type - Photoelectric
- Alarm Set Point - Fixed at 2.5% / ft (8%/m)
- Sensitivity Test Method - Self-diagnostic Test
- Air Velocity - 100 ft/min to 4000 ft/min
- Ambient Temperature - 32°F to 120°F (0°C to 49°C)
- Humidity - 10% to 85% Relative Humidity (Non-condensing)
- Housing Material - Plastic Backbox, Clear Plastic Cover
- Finish - Gray Backbox with Clear Cover
- Dimensions - 13 1/2”L x 4 1/2” W x 2 1/4” H
- Maximum Net Weight - 2 lbs.
- Sampling Tubes - 2.5 ft., 5 ft., or 10 ft.
- Relay Contact Rating - 8A@30VDC, 10A@120VAC, 10A@250VAC